• DocumentCode
    1646573
  • Title

    Electrical breakdown characteristics of the XLPE cables under AC, DC and pulsating voltages

  • Author

    Grzybowski, S. ; Fan, J.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Mississippi State Univ., MS, USA
  • Volume
    1
  • fYear
    1997
  • Firstpage
    389
  • Abstract
    Electrical breakdown strength of the 5 kV XLPE cables was studied under ac, dc and pulsating voltages. The pulsating voltage was obtained by superimposing ac voltage on dc voltage. In the later case, the ratio of ac to dc voltage components (p=Vac/Vdc) was varied between the limits of 0.1<p<10. Both the sound and imperfect cables are used as the test samples. Two types of imperfections are studied: Cables samples with artificial holes and cables samples with embedded needles. Study results shows that the pulsating voltage is an effective way to detect the imperfections inside the XLPE cables
  • Keywords
    XLPE insulation; electric breakdown; insulation testing; power cable insulation; power cable testing; 5 kV; AC voltage; DC voltage; XLPE cable; artificial hole; electrical breakdown strength; embedded needle; imperfection; pulsating voltage; Aging; Breakdown voltage; Cable insulation; Electric breakdown; Insulation testing; Laboratories; Needles; Oil insulation; Power transformer insulation; System testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1997., Proceedings of the 5th International Conference on
  • Conference_Location
    Seoul
  • Print_ISBN
    0-7803-2651-2
  • Type

    conf

  • DOI
    10.1109/ICPADM.1997.617618
  • Filename
    617618