• DocumentCode
    1646788
  • Title

    Negative strap corrosion in valve-regulated lead acid batteries and its analysis by accelerated life testing

  • Author

    Vaccaro, F.J. ; Rhoades, J. ; Malley, R. ; Le, B. ; Marion, K.

  • Author_Institution
    Power Battery Co. Inc., Paterson, NJ, USA
  • fYear
    1995
  • Firstpage
    70
  • Lastpage
    77
  • Abstract
    The corrosion and ultimate fracture of the negative strap of VRLA cells has resulted in open circuit battery strings. These open strings have caused loss of reserve power and service breaks in user equipment and systems. The expense and trauma of these interruptions have made it imperative to determine the cause for this corrosion and prevent it from occurring. This failure mechanism is not related to a previously well identified corrosion problem caused by differences in the antimony content between the strap alloy and plate lugs. It is the intent of this study to elucidate mechanisms that define the path to strap corrosion and failure, and to determine if the cures applied based on proposed failure mechanisms have eliminated the fracturing of negative straps. The effectiveness of the cures were evaluated in accelerated life tests and field service. One important result of this experimentation was the determination of an activation energy (AE) for strap corrosion. Comparison of this AE to that for other failure mechanisms revealed that hot testing may not reveal all failure mechanisms that occur at room temperature, and that remedies based on hot test studies may not achieve the desired results. This study included the following areas: strap quality and metallurgy; strap surface voltage and cathodic protection; and sodium sulfate additive
  • Keywords
    corrosion; corrosion protection; electrochemical electrodes; failure analysis; lead; life testing; secondary cells; Pb; Pb-acid valve regulated batteries; accelerated life testing; activation energy; antimony content; cathodic protection; failure mechanism; hot testing; negative strap corrosion; negative strap fracture; open circuit battery strings; plate lugs; reserve power loss; service breaks; sodium sulfate additive; strap alloy; strap metallurgy; strap quality; strap surface voltage; valve-regulated lead acid batteries; Acceleration; Batteries; Circuits; Corrosion; Failure analysis; Life estimation; Life testing; Protection; Temperature; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1995. INTELEC '95., 17th International
  • Conference_Location
    The Hague
  • Print_ISBN
    0-7803-2750-0
  • Type

    conf

  • DOI
    10.1109/INTLEC.1995.498932
  • Filename
    498932