    The effect of real network phase disturbances on the calculation of IEC 61000-4-30 parameters

  • Author

    Rens, Johan ; de Kock, Jan ; van Wyk, Willie ; van Zyl, Jacobus

  • Author_Institution
    Sch. for Electr. & Electron. Eng., North-West Univ., Potchefstroom, South Africa
  • fYear
    2014
  • fDate
    25-28 May 2014
  • Firstpage
    303
  • Lastpage
    306
  • Abstract
    Real life network dynamic phenomena are used to demonstrate how the calculation of IEC 61000-4-30 parameters can be affected. The voltage frequency can change instantaneously at a point in the network due to a shift in the position of zero crosses when large reactive power changes occur. Pseudo voltage swells can be recorded and spectral leakage incurred. It is proposed that a 10/12-cycle block value for frequency is used in addition to the IEC 61000-4-30 10-second values.
  • Keywords
    IEC standards; power supply quality; reactive power; IEC 61000-4-30 parameter calculation; Pseudo voltage swell; network phase disturbance; reactive power change; spectral leakage; voltage frequency; zero crosses position; IEC standards; Phase locked loops; Power system dynamics; Time-frequency analysis; Voltage measurement; ½-cycle rms; 10/12 cycle block; Class A; IEC 61000-4-30; Power quality; SVC; asynchronous sampling; minimum standards in quality of supply; phase-locked loop; spectral leakage; voltage frequency;