DocumentCode
164710
Title
IVTs behavior in SF6 switching transients: Fast front voltage impulse
Author
Grasselli, U. ; Lamedica, R. ; Sangiovanni, S. ; Ruvio, A. ; Cavarretta, M.C.
Author_Institution
Dept. Astronaut., Electr. & Energetic Eng. (DIAEE), Sapienza Univ. of Rome, Rome, Italy
fYear
2014
fDate
25-28 May 2014
Firstpage
823
Lastpage
827
Abstract
Instrument Voltage Transformers (IVTs) introduce errors in power quality measure due to resonance´s effects at high frequency. The accuracy of IVTs, definite by standards, is only about nominal frequency and does not consider high frequency response. The paper reports the IVTs experimental analysis on resonance´s disturbances transferred to secondary side of Instrument Voltage Transformer. In particular the main results obtained from a laboratory survey on three currently marketed IVTs with same features but different manufacture are presented. IVTs are tested with very fast front voltage impulse whose waveform is similar to the characteristic one of SF6 switches operations.
Keywords
potential transformers; power supply quality; switching transients; IVT; SF6 switching transients; instrument voltage transformer; nominal frequency; power quality measure; power quality measurements; voltage impulse; Frequency measurement; Power measurement; Power quality; Resonant frequency; Switches; Voltage measurement; Windings; High Frequency; Instrument Voltage Transformers; Power Quality; SF6 Switching Transients;
fLanguage
English
Publisher
ieee
Conference_Titel
Harmonics and Quality of Power (ICHQP), 2014 IEEE 16th International Conference on
Conference_Location
Bucharest
Type
conf
DOI
10.1109/ICHQP.2014.6842895
Filename
6842895