• DocumentCode
    1647929
  • Title

    The characteristics evolving from various VRLA battery designs

  • Author

    Harrison, A.I.

  • Author_Institution
    Hawker Batteries, Chloride Ind. Batteries Ltd., Swinton, UK
  • fYear
    1995
  • Firstpage
    346
  • Lastpage
    352
  • Abstract
    A review of valve-regulated Pb-acid (VRLA) battery Intelec papers 1982-1994 has identified four main areas of interest: developments; performance; theory; and operations. Development and operations are linked together insofar as operations describes the performance of batteries designed from developed VRLA products. Improvements in battery design and system operation are identified to minimise thermal problems. Changes in the internal construction of VRLAs have been reviewed which either directly or indirectly are designed to stabilise and reduce the level of float currents. Grid alloys with better corrosion resistance at elevated temperatures have been reported and their potential benefit to service life has been noted. The theoretical and performance papers constitute the largest contribution to papers published, and one third of this group have addressed the attributes and deficiencies pertaining to gelled versus AGM systems. A considerable amount of useful data has however been reported on the characteristics of VRLAs and this has been used to develop the concept that VRLAs should be considered in terms of the degree of electrolyte saturation within the cell. Using this concept and relationships between: electrolyte saturation; electrolyte specific gravity; overvoltage; open circuit voltage; and float voltage; simple models have been proposed to identify the scope of the characteristics arising within the various VRLA systems. The preferred model for UK telecommunications power supply is identified and experience in service since 1982 has justified this choice
  • Keywords
    electrochemical electrodes; electrochemistry; electrolytes; lead; secondary cells; telecommunication power supplies; Pb; Pb-acid secondary batteries; UK; battery design; characteristics; developments; electrolyte saturation; electrolyte specific gravity; float currents; float voltage; grid alloys; open circuit voltage; operations; overvoltage; performance; telecommunications power supply; theory; valve-regulated battery; Batteries; Circuits; Corrosion; Environmentally friendly manufacturing techniques; Gravity; Laboratories; Power system modeling; Temperature; Valves; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1995. INTELEC '95., 17th International
  • Conference_Location
    The Hague
  • Print_ISBN
    0-7803-2750-0
  • Type

    conf

  • DOI
    10.1109/INTLEC.1995.498974
  • Filename
    498974