DocumentCode
1661209
Title
Power Quality Investigation of Back-to-Back Harmonic Filters for a High-Voltage Anode Foil Manufacturing Facility
Author
Dionise, Thomas J. ; Lorch, Visuth ; Brazil, Brandon J.
Author_Institution
Eaton Electr. Power Syst. Eng., Warrendale
fYear
2007
Firstpage
1
Lastpage
8
Abstract
The problem, as described by this high-voltage anode foil manufacturing facility, has included loss of the harmonic filter banks during utility power disturbances. During such disturbances, one or more formation machine(s) trip and rectifier(s) fault, both of which are critical to the continuous operation of the process. One recent disturbance resulted in significant failure of components in both filter banks. A power quality investigation commenced to determine the cause of the filter bank failure. This paper describes the results of the analytical methods employed. Field harmonic measurements determined the presence of voltage and current distortion and established an appropriate model for harmonic analysis of various likely system conditions. Harmonic analysis explained the tuning of the existing filter banks and changes to tuning that occurred since installation several years ago, as well as determined the harmonic loading on each stage of the filters. Transient simulations identified existing problems and areas of concern, especially in regard to transient overvoltages that resulted when switching either of the filter banks. Recommendations included alternatives to avoid possible failures in the future, most significantly, the re-design of one the harmonic filters and the application of surge protection.
Keywords
channel bank filters; foils; metal product industries; power harmonic filters; production facilities; rectifying circuits; surge protection; back-to-back harmonic filter banks; field harmonic measurements; formation machine; harmonic loading; high-voltage anode foil manufacturing facility; rectifier fault; surge protection; transient overvoltages; transient simulations; utility power disturbances; voltage-current distortion; Anodes; Current measurement; Distortion measurement; Filter bank; Harmonic analysis; Harmonic filters; Power harmonic filters; Power quality; Production facilities; Surge protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Conference, 2007. 42nd IAS Annual Meeting. Conference Record of the 2007 IEEE
Conference_Location
New Orleans, LA
ISSN
0197-2618
Print_ISBN
978-1-4244-1259-4
Electronic_ISBN
0197-2618
Type
conf
DOI
10.1109/07IAS.2007.53
Filename
4347758
Link To Document