DocumentCode
1674219
Title
Grid sequence detector based on a stationary reference frame
Author
Robles, Eider ; Pou, Josep ; Ceballos, Salvador ; Gabiola, Igor ; Santos, Maider
Author_Institution
Robotiker-Tecnalia, Zamudio, Spain
fYear
2009
Firstpage
1
Lastpage
10
Abstract
This paper proposes a new three-phase positive sequence detector. The scheme is based on a stationary reference frame and a Moving Average Filter (MAF) that guarantees the complete cancellation of harmonics and grid imbalances. The performance of the MAF is mathematically analyzed and a proper selection of the optimal filter´s window width is realized. The proposed detector operates in open loop and there is no PI controller to be tuned. Thus, the dynamic response and simplicity is improved compared to other solutions. Performance of the proposed detector is verified through simulation and experiment. It shows very good performance under extreme grid voltage conditions, allowing fast detection of the grid voltage positive sequence (within one grid voltage cycle).
Keywords
PI control; power filters; power grids; power system harmonics; PI controller; grid sequence detector; grid voltage cycle; grid voltage positive sequence fast detection; moving average filter; stationary reference frame; three-phase positive sequence detector; Detectors; Finite impulse response filter; Frequency synchronization; Open loop systems; Performance analysis; Phase locked loops; Power harmonic filters; Robots; Uniform resource locators; Voltage; PLL; Sequence detector; grid connected power converters; grid voltage synchronization; moving average filter;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Applications, 2009. EPE '09. 13th European Conference on
Conference_Location
Barcelona
Print_ISBN
978-1-4244-4432-8
Electronic_ISBN
978-90-75815-13-9
Type
conf
Filename
5279258
Link To Document