Application of on-line versus off-line PD testing for stator insulation monitoring
Author :
Zhu, H. ; Green, V. ; Huynh, D.
Author_Institution :
ADWEL Int., Toronto, Ont., Canada
fYear :
1999
fDate :
6/21/1905 12:00:00 AM
Firstpage :
175
Lastpage :
178
Abstract :
Partial discharge testing can effectively diagnose insulation problems in the stator winding of high-voltage generators and motors, since partial discharges are a symptom of most insulation failure mechanisms. Partial discharge testing can be performed either when the machine is not operating (offline) or during normal machine operation (on-line). Off-line PD testing is a well-known method to assess the stator winding insulation. Over ten years, on-line PD testing has proven to be a successful technique of monitoring stator insulation condition to forewarn plant personnel of possible machine failures and to help them implement a predictive maintenance program. This paper presents an on-line and off-line PD test on a hydro-generator using the same test instrument and sensors. A comparison of the two tests indicates that the off-line test results are consistent with the on-line test results. Similarities and differences of the on-line and off-line PD tests are discussed
Keywords :
hydroelectric generators; insulation testing; machine insulation; partial discharge measurement; stators; high-voltage generators; high-voltage motors; hydro-generator; insulation failure mechanisms; off-line PD testing; on-line PD testing; partial discharge testing; possible machine failures; predictive maintenance program; stator insulation monitoring; stator winding; stator winding insulation; Condition monitoring; Couplers; Dielectrics and electrical insulation; Instruments; Insulation testing; Partial discharges; Stator windings; Thermal stresses; Voltage; Working environment noise;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, 1999. Proceedings
Conference_Location :
Cincinnati, OH
ISSN :
0362-2479
Print_ISBN :
0-7803-5757-4
Type :
conf
DOI :
10.1109/EEIC.1999.826202
Filename :
826202
Link To Document :
بازگشت