Power frequency electric and magnetic fields at a 110/20 kV substation
Author :
Isokorpi, J. ; Keikko, T. ; Korpinen, L.
Author_Institution :
Tampere Univ. of Technol., Finland
fYear :
1999
Firstpage :
169
Abstract :
The aim of this paper is to study electric and magnetic fields at a 110/20 kV substation. The fields were measured on the switchyard of the substation. Magnetic field measurements were carried out at two heights along two straight lines and on a quadrangular area. The currents in the conductors were also recorded during the measurements. The highest magnetic field was 18.6 /spl mu/T at the height of 1.0 m and 14.8 /spl mu/T at 0.5 m. Electric fields were measured at 1 m height on the same area and on two other lines. The highest electric field was 4.6 kV/m. The highest magnetic fields were caused by the crossing of a busbar and an outgoing feeder with the highest load, and by a 20 kV cable from the transformer to a 20 kV switchgear. The highest electric fields were caused by conductors passing below bus bars.
Keywords :
electric field measurement; electric fields; magnetic field measurement; magnetic fields; substations; 0.5 m; 1 m; 110 kV; 14.8 muT; 18.6 muT; 20 kV; busbar; conductor currents; electric field measurements; magnetic field measurements; outgoing feeder; power cable; power frequency EM fields; power transformer; substation; switchyard; Area measurement; Bars; Conductors; Current measurement; Electric variables measurement; Frequency; Magnetic field measurement; Magnetic fields; Substations; Switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
Conference_Location :
Budapest, Hungary
Print_ISBN :
0-7803-5836-8
Type :
conf
DOI :
10.1109/PTC.1999.826601
Filename :
826601
Link To Document :
بازگشت