• DocumentCode
    1683185
  • Title

    Impact of energization of large power transformer from weak source through ICT

  • Author

    Bandyopadhyay, Pratik ; Begum, Anisa

  • Author_Institution
    L&T-Sargent & Lundy Ltd., Vadodara, India
  • fYear
    2013
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents the impact of charging the large power transformer through a relatively weak source or grid via Interconnecting Transformer (ICT). The Generator transformer (GT) of power generating station needs to be back charged from the supply grid. Often, the permanent grid supply is not available to charge the GT at the time of commissioning and there is a practice to temporarily connect lower voltage grid through ICT. The purpose of this study is to evaluate the impact of GT charging on power system network and on ICTs and provide guidelines for proper selection of ICTs. Simulation is done on PSCAD and results are verified with recorded results observed at site during actual charging of GT.
  • Keywords
    power grids; power transformers; ICT; PSCAD; generator transformer; interconnecting transformer; large power transformer; permanent grid supply; power generating station; power system network; supply grid; weak source; Circuit faults; Harmonic analysis; PSCAD; Power transformers; Relays; Simulation; Surges; GT; ICT; charging; energization; power transformer; source impedance; weak source;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Engineering (NUiCONE), 2013 Nirma University International Conference on
  • Conference_Location
    Ahmedabad
  • Print_ISBN
    978-1-4799-0726-7
  • Type

    conf

  • DOI
    10.1109/NUiCONE.2013.6780163
  • Filename
    6780163