• DocumentCode
    1683548
  • Title

    Breakdown characteristics of CO/sub 2/ and N/sub 2/ containing SF/sub 6/ at different gap spacings

  • Author

    Onal, Emrah ; Kalenderli, O. ; Mardikyan, K.

  • Author_Institution
    Fac. Electr. Eng., Istanbul Tech. Univ., Turkey
  • fYear
    1999
  • Firstpage
    203
  • Abstract
    AC breakdown strengths of CO/sub 2/, N/sub 2/, SF/sub 6/ and the mixtures of CO/sub 2/+SF/sub 6/ and N/sub 2/+SF/sub 6/ containing 0.5% and 4% of SF/sub 6/ in a nonuniform field were experimentally studied. The relative gas pressure and the electrode gap spacing were varied within the range of 100-500 kPa and of 5-20 mm respectively. The experimental results have shown that the addition of SF/sub 6/ to CO/sub 2/ and N/sub 2/ causes a significant increase the AC breakdown voltage with respect to CO/sub 2/ and N/sub 2/.
  • Keywords
    SF/sub 6/ insulation; carbon compounds; electric breakdown; gas mixtures; insulation testing; nitrogen; 100 to 500 kPa; 5 to 20 mm; AC breakdown strengths; AC breakdown voltage; CO/sub 2/; N/sub 2/; SF/sub 6/; breakdown characteristics; electrode gap spacing; nonuniform field; relative gas pressure; Biographies; Breakdown voltage; Dielectrics and electrical insulation; Electric breakdown; Electrodes; High-voltage techniques; Linear approximation; Pressure measurement; Sulfur hexafluoride; System testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
  • Conference_Location
    Budapest, Hungary
  • Print_ISBN
    0-7803-5836-8
  • Type

    conf

  • DOI
    10.1109/PTC.1999.826635
  • Filename
    826635