The influence of fault current limiting in power systems on transient recovery voltage
Author :
Zissu, S. ; Shein, D.
Author_Institution :
Res. & Dev. Div., Israel Electr. Corp. Ltd., Haifa, Israel
fYear :
1996
Firstpage :
479
Lastpage :
482
Abstract :
This paper investigates the influence of some means to limit the short-circuit current level (busbars splitting in switchgear substations or the transformer windings grounding) on the circuit breakers capability, from the point of view of transient recovery voltage (TRV). An approach for TRV evaluation was developed (based on the EMTP program usage) and applied for two SF6 switchgear substations
Keywords :
SF6 insulation; busbars; current limiters; power system transients; power transformers; short-circuit currents; switchgear testing; switching substations; transformer windings; EMTP program usage; SF6; SF6 switchgear substations; busbars splitting; circuit breakers capability; fault clearing; fault current limiting; power systems; short-circuit current level; transformer windings grounding; transient recovery voltage; Circuit breakers; EMTP; Fault currents; Grounding; Power system faults; Power system transients; Substations; Switchgear; Transient analysis; Windings;