Title :
Calculation of the impedances of underground lines seen by distance protections
Author :
Leitloff, V. ; Bourgent, X. ; Dubne, G.
Author_Institution :
Electr. de France, Clamart, France
Abstract :
Meshed underground networks pose particular problems for network protection. If distance protection is used to protect cable networks, a good knowledge of the impedances is important. It is not possible to give a simple relation for the sequence impedances for all types of single core (single-phase) cables if the fault is on the underground line itself. This is due to the fact that, for this case, 6 or 7 independent conductors [3 phases+3 screens+(optional) 1 ground wire] have to be taken into account. This paper presents a model able to determine the impedances seen by distance protections for faults on the cable and discusses the findings.
Keywords :
electric impedance; power cables; power transmission faults; power transmission protection; underground cables; underground transmission systems; cable networks protection; distance protection; impedances calculation; independent conductors; meshed underground networks; single core single-phase cables; underground lines; Cables; Conductors; Fault location; Grounding; Impedance measurement; Particle measurements; Protection; Research and development; Substations; Wire;
Conference_Titel :
Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
Conference_Location :
Budapest, Hungary
Print_ISBN :
0-7803-5836-8
DOI :
10.1109/PTC.1999.826640