Influence of MV distribution networks structure on voltage dips propagation
Author
Ala, G. ; Barone, A.B. ; Favuzza, S. ; Inzerillo, M.
Author_Institution
Dept. of Electr. Eng., Palermo Univ., Italy
fYear
1999
Firstpage
221
Abstract
In this paper, transient behaviour due to voltage dips which occur in electric power MV distribution networks as a consequence of a fault by using an improved ATP circuit-breaker model are reported. The circuit-breaker is simulated by using a tool written in MODELS language and by arranging a time-variable differential arc-conductance based on the combination of Mayr´s and Cassie´s equations. An accurate analysis of the transient subsequent to circuit-breaker operation, in different fault conditions, are reported in order to show how the amplitude of the dip depends on the fault type, location and network structure.
Keywords
circuit breakers; circuit-breaking arcs; power distribution faults; power system transients; ATP circuit-breaker model; Cassie equation; MODELS language; MV distribution networks structure; Mayr equation; circuit-breaker simulation; fault location; time-variable differential arc-conductance; transient behaviour; voltage dips propagation; Circuit faults; Circuit simulation; Differential equations; Electronics packaging; Power system dynamics; Power system protection; Power system simulation; Power system transients; Transient analysis; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
Conference_Location
Budapest, Hungary
Print_ISBN
0-7803-5836-8
Type
conf
DOI
10.1109/PTC.1999.826653
Filename
826653
Link To Document