DocumentCode :
1685719
Title :
Power factor correction for intermittent and fluctuating loads
Author :
Attia, I. ; Youssef, K. ; Tantawy, M. ; Bekheet, M.
Author_Institution :
Alexandria Electr. Co., Egypt
fYear :
1999
Firstpage :
289
Abstract :
This paper reports case studies of capacitors for marble plant application, as an example of time varying loads. The marble process depends largely upon the thickness and polished surface of the marble block. During the cutting and polishing processes, these conditions cause strictly time-varying active and reactive power and also produce unbalanced varying load at low varying power factors. This paper presents the measurement results of an electrical parameter survey of marble loads. It also discusses the selection of capacitor banks according to harmonic currents.
Keywords :
harmonic distortion; industrial power systems; load (electric); power capacitors; power factor correction; power supply quality; power system harmonics; capacitor banks selection; case studies; cutting process; electrical parameter survey; fluctuating loads; harmonic currents; intermittent loads; low varying power factors; marble plant application; polishing process; power capacitors; power factor correction; time varying loads; time-varying active power; time-varying reactive power; unbalanced varying load; Capacitors; Electric variables measurement; Inductors; Pollution measurement; Power factor correction; Power measurement; Power quality; Power system harmonics; Reactive power; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electric Power Engineering, 1999. PowerTech Budapest 99. International Conference on
Conference_Location :
Budapest, Hungary
Print_ISBN :
0-7803-5836-8
Type :
conf
DOI :
10.1109/PTC.1999.826721
Filename :
826721
Link To Document :
بازگشت