    Development of interrupting chamber for 1000 kV HSGS with a delayed-zero-current interrupting performance

  • Author

    Yamagata, Y. ; Tanaka, K. ; Terasawa, Y. ; Shinkai, T. ; Mizoguchi, H. ; Hioki, I. ; Suzuki, K. ; Yokota, T.

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    1
  • fYear
    1995
  • Firstpage
    404
  • Abstract
    High speed grounding switches (HSGS) for 1000 kV class transmission lines are required to interrupt a delayed-zero-current, which does not pass zero for more than 80 ms under particular fault conditions. A new interrupting chamber has been developed with an ability of keeping a gas blast for more than 80 ms. New testing methods have been investigated with the aim of testing the delayed-zero-current interrupting performance of the HSGS
  • Keywords
    earthing; gas blast circuit breakers; switchgear testing; 1000 kV; delayed-zero-current interrupting performance; fault conditions; gas blast; high speed grounding switches; interrupting chamber; testing methods; Circuit faults; Circuit stability; Delay effects; Electromagnetic induction; Electrostatic induction; Fault currents; Fluid flow; Gas insulation; Impedance; Temperature control;