DocumentCode :
1690666
Title :
A three-phase four-line soft switched inverter for UPS applications
Author :
Yu, Zhao ; Yangguang, Yan
Author_Institution :
Dept. of Automatic Control, Nanjing Aeronaut. Inst., China
fYear :
1992
Firstpage :
696
Abstract :
As the heart of UPS systems, the inverter is required to cope with stringent voltage regulation and distortion constraints in the presence of unbalanced and nonlinear loads. This paper presents a four-leg soft switched inverter topology to provide a four-line output including the neutral point. The adoption of a resonant DC link inverter (RDCLI) technique, which makes the four-line output possible, offers the potential of substantially higher switching frequency resulting in high reliability, high power densities and high quality AC power. A novel controller is proposed to achieve excellent static and transient performance characteristics. This inverter system has been studied in detail by simulation, including the use of an active clamp circuit, a new kind of discrete pulse current regulator, a load current feedforward strategy under different load conditions
Keywords :
invertors; load (electric); network analysis; switching circuits; uninterruptible power supplies; UPS; active clamp circuit; applications; discrete pulse current regulator; distortion; four-line output; load current feedforward strategy; neutral point; nonlinear loads; performance characteristics; reliability; resonant DC link inverter; soft switched inverter; switching frequency; three-phase; unbalanced loads; voltage regulation; Circuit simulation; Heart; Inverters; Nonlinear distortion; Power system reliability; Resonance; Switching frequency; Topology; Uninterruptible power systems; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial Electronics, 1992., Proceedings of the IEEE International Symposium on
Conference_Location :
Xian
Print_ISBN :
0-7803-0042-4
Type :
conf
DOI :
10.1109/ISIE.1992.279693
Filename :
279693
Link To Document :
بازگشت