DocumentCode :
1691650
Title :
Unbalanced short-circuit calculation by phase coordinates
Author :
He, W.X. ; Teo, C.Y.
Author_Institution :
Sch. of Electr. & Electron. Eng., Nanyang Technol. Univ., Singapore
Volume :
2
fYear :
1995
Firstpage :
744
Abstract :
This paper demonstrates a direct approach for fault current calculations without using symmetrical components. By representing a polyphase network in phase-coordinates, i.e. phase voltages, currents and impedances, the unbalanced fault currents can also be analyzed and calculated. The proposed approach is direct and can be implemented easily by solving a set of linear system equations. Identical results for both methods are obtained in a sample network. The following faults are analyzed: phase-to-earth with/without impedance; phase-to-phase fault with/without impedance; two-phase-to-earth fault; and a three-phase fault
Keywords :
electric impedance; fault diagnosis; power systems; short-circuit currents; fault analysis; fault current calculations; linear system equations; phase coordinates; phase currents; phase impedances; phase voltages; phase-to-earth fault; phase-to-phase fault; polyphase network; three-phase fault; two-phase-to-earth fault; unbalanced short-circuit calculation; Admittance; Differential equations; Distributed parameter circuits; Fault currents; Helium; Impedance; Mutual coupling; Power system modeling; Transmission line matrix methods; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Management and Power Delivery, 1995. Proceedings of EMPD '95., 1995 International Conference on
Print_ISBN :
0-7803-2981-3
Type :
conf
DOI :
10.1109/EMPD.1995.500821
Filename :
500821
Link To Document :
بازگشت