DocumentCode :
1693508
Title :
Reduce the factor of space humidity on the incorrect action of circuit breakers
Author :
Song Dan ; Cao Yaxu ; Xu Hui
Author_Institution :
Henan Zhengzhou Power Supply Co., Zhengzhou, China
Volume :
1
fYear :
2011
Firstpage :
93
Lastpage :
96
Abstract :
The design of modern circuit breakers precision, excellent quality, its own causes a very small probability of incorrect action, but external factors such as the daily average relative humidity is too high in certain space will cause circuit breaker malfunction or refuse to move. Outdoor mechanism housing, the Department of substation control cabinet is an important device, the internal components play a power, control, measurement and protection, if the outdoor substation mechanism housing, the Department of the internal control cabinet more than the daily average relative humidity 70% dew point condensation phenomena occur may lead to DC ground, AC discharge or short circuit occurs, the circuit breaker Malfunction or refuse to move, there are serious hidden dangers, and even the entire power grid of outdoor substation security and stability of a threat. In this paper, the change of temperature, rainfall, the use of heater and the seal of mechanism housing, cable channel water damp and other aspects of impact of the outdoor substation mechanism box´s average relative humidity will be analyzed, and a series of effective measures to control the chamber humidity, down to 70% (dew point) to avoid outdoor mechanism housing´s high space humidity causing circuit breaker malfunction, refused to move, which do not state the correct action.
Keywords :
circuit breakers; power grids; probability; substation protection; AC discharge; DC ground; cable channel water damp; chamber humidity; circuit breaker malfunction; daily average relative humidity; internal components; outdoor mechanism housing; outdoor mechanism housing high space humidity avoidance; outdoor substation mechanism box average relative humidity; outdoor substation mechanism housing; outdoor substation security; power grid; probability; space humidity factor; substation control cabinet department; Automation; Circuit breakers; Humidity; Power cables; Semiconductor device measurement; Substations; Temperature control; condensation phenomena; daily average relative humidity; mechanism housing; semiconductor dehumidification;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9622-8
Type :
conf
DOI :
10.1109/APAP.2011.6180392
Filename :
6180392
Link To Document :