Title :
Permanent faults identification for three-phase autoreclosure on transmission lines with shunt reactors
Author :
Suonan Jiale ; Liang ZhenFeng ; Song Guobing ; Kang Xiaoning
Author_Institution :
Xi´an Jiaotong Univ., Xian, China
Abstract :
Auto-reclosure technique applied to transmission lines is an effective method to improve stability of power system. In this paper, a novel three-phase adaptive reclosure method by estimating shunt reactors parameter was developed to distinguish permanent fault from transient fault for transmission line with shunt reactors. The method employs the shunt reactor currents during dead time to build parameter estimation functions. The difference between the estimated value and the actual one is evaluated for distinguishing permanent fault from transient fault. EMTP simulations show the correctness and validity of the proposed method.
Keywords :
parameter estimation; power system stability; power transmission faults; power transmission lines; EMTP simulations; permanent fault identification; power system stability; shunt reactor parameter estimation; shunt reactors; three-phase adaptive reclosure method; three-phase autoreclosure; transmission lines; Circuit faults; Inductors; Mathematical model; Power transmission lines; Shunt (electrical); Transient analysis; parameter estimation; power system; relaying protection; shunt reactors; three-phase adaptive reclosure; transmission line;
Conference_Titel :
Advanced Power System Automation and Protection (APAP), 2011 International Conference on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-9622-8
DOI :
10.1109/APAP.2011.6180404