Title :
Static-digital overcurrent relays permit enhanced protection
Author :
Bailey, Bruce ; Jakominich, Dan
Author_Institution :
Siemens Power Transmission & Distribution, Raleigh, NC, USA
Abstract :
Multi-function static overcurrent relays employing digital technology have functionality that permits improved and expanded protection in many applications. While a relay is normally selected for the required overcurrent and ground fault protection, effective utilization of additional available functions can provide added security without significant additional cost. This paper describes an application for an oil refinery power system that uses directional overcurrent elements and reverse interlocking between the main, tie and feeder relays for a dual source-normally closed tie system. This scheme provides fast tripping for bus faults, which has several advantages over traditional bus differential relaying. This paper also describes a ground fault protection scheme to detect feeder grounds on a high resistance grounded system
Keywords :
distribution networks; earthing; electrical faults; industrial power systems; oil refining; overcurrent protection; power system protection; power system relaying; power system security; relay protection; bus fault tripping; distribution network protection; feeder grounds detection; ground fault protection; multi-function static overcurrent relays; oil refinery power system; reverse interlocking; security; Circuit faults; Delay effects; Digital relays; Fault detection; Monitoring; Power system protection; Power system relaying; Power system security; Protective relaying; Senior members;
Conference_Titel :
Industrial and Commercial Power Systems Technical Conference, 1998 IEEE
Conference_Location :
Edmonton, Alta.
Print_ISBN :
0-7803-4509-6
DOI :
10.1109/ICPS.1998.692529