  • Abstract
    Conducted electromagnetic interference (EMI) due to the operation of HVDC converter station is caused by the processes during ignition and extinction of the thyristors in the converter valves. A method is developed in this paper for calculating the EMI level of the 12-pulse plusmn500 kV converter stations. In this method, the main equipments of the converter station are modeled and connected. The stray capacitances are considered in this model. A comparison is conducted between the measured and simulated. From some typical waveforms obtained by this paper, it is found that the high frequency components of the electromagnetic field radiated by the valve are caused by the snubber circuits.
  • Keywords
    HVDC power convertors; electromagnetic interference; snubbers; substations; thyristor applications; HVDC converter station; conductive electromagnetic interference; converter valves; snubber circuits; stray capacitances; thyristor extinction; thyristor ignition; voltage -500 kV to 500 kV; Capacitance; Circuit simulation; Electromagnetic fields; Electromagnetic interference; Electromagnetic measurements; Frequency; HVDC transmission; Ignition; Thyristors; Valves;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Automation Congress, 2008. WAC 2008. World
  • Conference_Location
    Hawaii, HI
  • Print_ISBN
    978-1-889335-38-4
  • Electronic_ISBN
    978-1-889335-37-7
  • Type

    conf

  • Filename
    4699118