• DocumentCode
    1699678
  • Title

    Failure mode for AC drives on high resistance grounded systems

  • Author

    Tallam, Rangarajan M. ; Schlegel, David W. ; Hoadley, Frederick L.

  • Author_Institution
    Rockwell Autom., Mequon, WI
  • fYear
    2006
  • Abstract
    High resistance grounding (HRG) is the preferred method of grounding in several industrial power distribution systems because of safety and reliability concerns. In this paper, a failure mode for AC drives on HRG systems is investigated. The cause of the failure is identified to be due to the interaction between the EMC circuitry of the drives. Simulation and experimental results are provided to demonstrate the failure mode. User manuals of several drive manufacturers are reviewed and recommendations for operating drives on HRG systems are provided
  • Keywords
    earthing; electric drives; electromagnetic compatibility; failure analysis; power system reliability; AC drives; EMC circuitry; HRG systems; failure mode; high resistance grounding systems; Circuit faults; Electromagnetic compatibility; Grounding; Manufacturing; Personnel; Power distribution; Power system reliability; Power system simulation; Safety; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Applied Power Electronics Conference and Exposition, 2006. APEC '06. Twenty-First Annual IEEE
  • Conference_Location
    Dallas, TX
  • Print_ISBN
    0-7803-9547-6
  • Type

    conf

  • DOI
    10.1109/APEC.2006.1620752
  • Filename
    1620752