DocumentCode
1699678
Title
Failure mode for AC drives on high resistance grounded systems
Author
Tallam, Rangarajan M. ; Schlegel, David W. ; Hoadley, Frederick L.
Author_Institution
Rockwell Autom., Mequon, WI
fYear
2006
Abstract
High resistance grounding (HRG) is the preferred method of grounding in several industrial power distribution systems because of safety and reliability concerns. In this paper, a failure mode for AC drives on HRG systems is investigated. The cause of the failure is identified to be due to the interaction between the EMC circuitry of the drives. Simulation and experimental results are provided to demonstrate the failure mode. User manuals of several drive manufacturers are reviewed and recommendations for operating drives on HRG systems are provided
Keywords
earthing; electric drives; electromagnetic compatibility; failure analysis; power system reliability; AC drives; EMC circuitry; HRG systems; failure mode; high resistance grounding systems; Circuit faults; Electromagnetic compatibility; Grounding; Manufacturing; Personnel; Power distribution; Power system reliability; Power system simulation; Safety; Voltage;