• DocumentCode
    1703304
  • Title

    Measured Impedance by Distance Relay Considering Double Model of the Line Capacitance

  • Author

    Jamali, S. ; Shateri, H.

  • Author_Institution
    Dept. of Electr. Eng., Center of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
  • fYear
    2006
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    This paper investigate the measured impedance by distance relay considering the transmission line capacitance by utilizing a double pi model for the line. The distance relay ideal tripping characteristic is therefore presented. The measured impedance and the tripping characteristic are compared with those in the case of not considering the line capacitance. In the case of zero fault resistance, the deviation of the measured impedance from its exact value caused by the line capacitance is also investigated.
  • Keywords
    electric impedance measurement; power transmission faults; power transmission lines; power transmission protection; relay protection; distance relay; double pi model; impedance measurement; relay tripping characteristics; transmission line capacitance; Capacitance measurement; Circuit faults; Electrical resistance measurement; Impedance measurement; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying; Transmission line measurements; Distance protection; Fault resistance; Line capacitance; Measured impedance; Transmission line;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power System Technology, 2006. PowerCon 2006. International Conference on
  • Conference_Location
    Chongqing
  • Print_ISBN
    1-4244-0110-0
  • Electronic_ISBN
    1-4244-0111-9
  • Type

    conf

  • DOI
    10.1109/ICPST.2006.321903
  • Filename
    4116062