A Novel Current Differential Protection Scheme for Powerformer
Author
Tian, Qing ; Lin, Xiangning ; Lu, Wenjun
Author_Institution
Coll. of Electr. & Electron. Eng., Huazhong Univ. of Sci. & Technol., Wuhan
fYear
2006
Firstpage
1
Lastpage
7
Abstract
This paper presents a novel differential protection of power former, a type of high-voltage graded insulated cable wound generator. The false differential current associated with the distributed capacitance of power former stator windings is analyzed. Based on the investigation results, the winding capacitance can be equivalently arranged on the terminal and neutral of the generator respectively in a reasonable partition. And the phase voltages at the terminals are utilized to estimate the capacitive currents, which can be compensated to improve the sensitivity of the differential protection. Extensive simulation results prove that this compensation scheme can improve the reliability of the current differential protection of power former.
Keywords
power transformer protection; stators; synchronous generators; AC synchronous generators; capacitive current estimation; current differential protection reliability; distributed capacitance; false differential current; high-voltage graded insulated cable wound generator; powerformer stator winding; winding capacitance; Cable insulation; Capacitance; Power cable insulation; Power cables; Power generation; Power system protection; Power transformer insulation; Power transmission lines; Stator windings; Voltage; cable capacitance; graded insulation; powerformer; self-adaptive compensated;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2006. PowerCon 2006. International Conference on
Conference_Location
Chongqing
Print_ISBN
1-4244-0110-0
Electronic_ISBN
1-4244-0111-9
Type
conf
DOI
10.1109/ICPST.2006.321478
Filename
4116104
Link To Document