Title
The Development of Arc-suppression Line Selection Device Based on PC104
Author
Xu, Youdong ; Guo, Zhenhong ; Zhang, Mingmei ; Wang, Xinkuan
Author_Institution
Chongqing Electr. Power Corp., Chongqing
fYear
2006
Firstpage
1
Lastpage
6
Abstract
This paper gives the characteristics of single-phase earth fault and ferro-resonance, then proposes two methods that adopt restricting the recovery rate of fault phase voltage to replace the Peterson-coil: using metal-oxide nonlinear resistance to extinguish electric arc, or making the fault phase metallic grounded, then the ferro-resonance which is more harm to system is changed into metallic grounded fault. After that, this paper proposes that changes the parameter of system instantaneously, as adding fault information to select out fault line. At last, this paper gives a design of the device based on PC104, and introduces its action mechanism and diagram. It also gives the hardware scheme and software design: including the criterion of fault judgment and algorithm of line selection, extinguishing the electric arc and the realization of line selection.
Keywords
arcs (electric); earthing; ferroresonance; power engineering computing; PC 104; arc-suppression line selection device; electric arc; ferro-resonance; metal-oxide nonlinear resistance; metallic grounded fault; single-phase earth fault; Cables; Capacitance; Earth; Electric resistance; Fault currents; Ferroresonance; Hardware; Power system faults; Power system reliability; Voltage control; PC104; arc-suppression; fault line selection; single-phase earth fault;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2006. PowerCon 2006. International Conference on
Conference_Location
Chongqing
Print_ISBN
1-4244-0110-0
Electronic_ISBN
1-4244-0111-9
Type
conf
DOI
10.1109/ICPST.2006.321616
Filename
4116130
Link To Document