• DocumentCode
    1708088
  • Title

    Load rates of low voltage transformers and medium voltage profile assessments on a real distribution electric grid based on average Daily Load Profile (DLP) of a housing for a high penetration of plug-in hybrid electric vehicles (PHEVs)

  • Author

    Turker, H. ; Florescu, A. ; Bacha, S. ; Chatroux, D.

  • Author_Institution
    Grenoble Electr. Eng. Lab. (G2ELAB), Grenoble, France
  • fYear
    2011
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This paper assesses the impact of PHEVs on a real medium voltage distribution electric grid based on average Daily Loads Profiles (DLPs) of a PHEV and of a housing. For three penetration rates, we show the important effects on load rates of low voltage transformers which compose the studied urban substation. Nevertheless, we demonstrate the robustness of medium voltage electric grid for the high penetration of PHEVs because the ηV index proposed which assess the quality of the voltage supplied to low voltage transformers reached a minimum of 98.2%.
  • Keywords
    hybrid electric vehicles; potential transformers; power grids; substations; average daily load profile; load rates; low voltage transformers; medium voltage profile assessments; plug-in hybrid electric vehicles; real distribution electric grid; real medium voltage distribution; urban substation; Databases; Low voltage; Mathematical model; Substations; System-on-a-chip; Vehicles; Water heating; Daily Load Profile; Distribution electric grid; Housing; Load rate; Low voltage transformer; Penetration rate; Plug-in Hybrid Electric Vehicle; Substation; Voltage quality;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Vehicle Power and Propulsion Conference (VPPC), 2011 IEEE
  • Conference_Location
    Chicago, IL
  • ISSN
    Pending
  • Print_ISBN
    978-1-61284-248-6
  • Electronic_ISBN
    Pending
  • Type

    conf

  • DOI
    10.1109/VPPC.2011.6043114
  • Filename
    6043114