Title
Enabling 11/500 kV test transformer for 11 kV equipment testing
Author
Amin, Muhammad
Author_Institution
Univ. of Eng. & Technol., Pakistan
Volume
2
fYear
2005
Firstpage
429
Abstract
This paper presents a solution to the problem of quasi-steady-state over voltages occurring across 11/500 kV test transformer (originally designed to solve the insulator contamination problem/design in deserts and coastal areas), thereby making it suitable for separate source voltage withstand tests of equipment with rated voltage of 11 kV and below. Further, it also presents a theoretical and experimental analysis of the recovery over voltages and means to prevent their occurrence. Besides, frequency response, harmonic analysis of the saturation impulse current and behaviour of the delay cable adequately supported with mathematical models/digital simulations were also carried out. The agreement between the results of experimental and those by analytical method, in certain cases, enabled to devise methods for prevention of initial and recovery over voltages on the test system.
Keywords
frequency response; harmonic analysis; insulator contamination; insulator testing; overvoltage protection; power transformer insulation; power transformer protection; power transformer testing; 11 kV; 500 kV; digital simulations; frequency response; harmonic analysis; insulator contamination problem; mathematical models; over voltage prevention; quasi-steady-state over voltages; recovery over voltages; saturation impulse current; transformer testing; Circuit faults; Contamination; Delay; Frequency response; Harmonic analysis; Insulator testing; Mathematical model; Power transformer insulation; Sea measurements; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials, 2005. (ISEIM 2005). Proceedings of 2005 International Symposium on
Print_ISBN
4-88686-063-X
Type
conf
DOI
10.1109/ISEIM.2005.193580
Filename
1496180
Link To Document