DocumentCode :
1714478
Title :
Voltage Distribution Effects of Non-Uniform Units in Suspension Strings
Author :
Ilhan, Suat ; Ozdemir, Aydogan
Author_Institution :
Istanbul Tech. Univ., Istanbul
fYear :
2007
Firstpage :
801
Lastpage :
806
Abstract :
10 unit and 22-unit cap-and-pin type insulator strings are used in 154 kV and 380 kV Turkish national power transmission systems. Turkish national electric power transmission utility staff prefer replacing the damaged units by stronger fog-type ones to minimize the transient outages resulting because of the insulation problems at the lower and upper units in the string. However, it is obvious that such a replacement changes the voltage distribution of the string composed of identical units. This change depends on the several parameters. This study presents the simulation results of voltage distribution along a 10-unit suspension string and 22-unit suspension string. Studies were conducted for the strings composed of different types of units for different tower designs and different contamination cases under power frequency voltages and lightning impulse voltages.
Keywords :
insulators; poles and towers; transient analysis; Turkish national power transmission systems; cap-and-pin type insulator strings; insulation problems; lightning impulse voltages; nonuniform units; suspension strings; tower designs; transient outages; voltage 154 kV; voltage 380 kV; voltage distribution; voltage distribution effects; Capacitance; Contamination; Flashover; Frequency; Insulation; Lightning; Poles and towers; Power system transients; Power transmission; Voltage; Non-uniform units; shunt capacitances; string insulator; voltage distribution;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech, 2007 IEEE Lausanne
Conference_Location :
Lausanne
Print_ISBN :
978-1-4244-2189-3
Electronic_ISBN :
978-1-4244-2190-9
Type :
conf
DOI :
10.1109/PCT.2007.4538418
Filename :
4538418
Link To Document :
بازگشت