    Determination of the saturated inductance of transformers by analytical formulae, comparison with an electromagnetic field calculation approach and validation by on-site tests.

  • Author

    Rioual, Michel ; Guillot, Yves ; Crépy, Cyrille

  • Author_Institution
    EDF R&D, Clamart, France
  • fYear
    2009
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This document describes the determination of the saturated inductance of a transformer, which is the slope of the saturation curve Phi(I) under highly saturated conditions. This parameter, which has a strong impact on the overvoltages when energizing a transformer, has been determined from analytic formulae for a shell-type transformer. Comparisons with the values derived from an electromagnetic 3D calculation and on-site tests are also given in this paper.
  • Keywords
    computational electromagnetics; inductance; transformers; analytical formulae; electromagnetic 3D calculation; electromagnetic field calculation; on-site tests; overvoltages; shell-type transformer; transformers saturated inductance determination; Electric resistance; Electromagnetic analysis; Electromagnetic fields; IEC standards; Inductance; Magnetic circuits; Magnetic cores; Surges; Testing; Transformers; Energization; air-core inductance; core-type; inrush currents; power transformers; saturated inductance; shell-type;