    A Method for Optimally Localizing Power Quality Monitoring Devices in Power Systems

  • Author

    Dzienis, C. ; Komarnicki, P. ; Styczynski, Z.A.

  • Author_Institution
    Otto von Guericke Univ., Magdeburg
  • fYear
    2007
  • Firstpage
    1522
  • Lastpage
    1527
  • Abstract
    This paper presents a method for optimally localizing power quality monitoring devices in power systems. The method is based on calculating the load flow in the frequency domain. The computation algorithm also obtains the Jacobi matrix that reflects the working point of a power system. Singular value decomposition enables obtaining information about nodes sensitive to harmonic. These nodes are where the power quality monitoring systems should be installed.
  • Keywords
    Jacobian matrices; frequency-domain analysis; load flow; power apparatus; power supply quality; power system measurement; Jacobi matrix; load flow; optimally power quality monitoring devices; singular value decomposition; Harmonic analysis; Iterative algorithms; Jacobian matrices; Load flow; Monitoring; Power measurement; Power quality; Power system harmonics; Power system modeling; Power systems; Harmonic Load Flow; Modeling; Power Quality Monitoring System; Singular Value Decomposition;