DocumentCode
171771
Title
Performance of reinforcing-steel with joints for down-conductors and resistance of a building where rebar and joints were connected by connectors
Author
Hiruma, Kazuo ; Sonehara, Takeo ; Nihei, Takayuki ; Yokoyama, Shiyoshi ; Shimokawa, Hiroaki
Author_Institution
Mech. & Electr. Design Dept., Obayashi Corp., Japan
fYear
2014
fDate
11-18 Oct. 2014
Firstpage
74
Lastpage
81
Abstract
The Investigation and Research Committee of the Institute of Electrical Installation Engineers of Japan evaluated the performance of rebar used in the construction of buildings as down-conductors for lightning protection and determined that lightning current can be made to flow through rebar and joints that meet requirements. The authors measured the resistance of a building where rebar and joints were connected by lightning connectors and proved that the resistance was very low.
Keywords
building management systems; electric connectors; lightning protection; steel; building construction; building resistance; down-conductors; joints; lightning connectors; lightning current; lightning protection; rebar; reinforcing-steel performance; Conductors; Connectors; Inductors; Instruments; Joints; Mortar; Resistors; connector; down-conductor; joint; lightning protection; rebar;