Lightning caused outages in the Austrian Power Grid transmission line network
Author :
Diendorfer, Gerhard ; Pichler, Hannes ; Achleitner, G. ; Broneder, Matthias
Author_Institution :
Dept. ALDIS, Austrian Electrotech. Assoc., Vienna, Austria
fYear :
2014
fDate :
11-18 Oct. 2014
Firstpage :
152
Lastpage :
156
Abstract :
Austria is one of the European countries with relatively high lightning activity [1] and lightning is a main cause of transmission line outages. In this presentation we have analyzed in detail lightning caused outages in the grid of the Austrian transmission system operator Austrian Power Grid (APG). 222 outage related lightning flashes were identified in the database of the Austrian lightning location system ALDIS as these flashes were located within a corridor of ±1 km along the considered lines and within a time window of ±1 second of the recorded outage time. These 222 flashes (203 of negative and 19 of positive polarity) are analyzed in terms of their local occurrence along the transmission lines and their peak currents. Tower footing resistances, which are affecting the occurrence of back flashover failures, were found to be log-normal distributed with a median of 4.4 Ω and a σln = 1.1. Median peak current of negative and positive flashes causing transmission line outages is -11.3 kA and 37.9 kA, respectively, and median distance of flash locations to the line is 322 m.
Keywords :
failure analysis; flashover; lightning protection; log normal distribution; power grids; power transmission lines; power transmission protection; ALDIS; APG; Austrian lightning location system; Austrian power grid transmission line network; Austrian transmission system operator; back flashover failures; current -11.3 kA; current 37.9 kA; distance 322 m; lightning caused outages; log-normal distribution; negative flashes; outage related lightning flashes; positive flashes; tower footing resistances; transmission line outages; Databases; Lightning; Poles and towers; Lightning; Lightning Location; Shielding Failure; Tower Footing Resistance; Transmission Line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
Type :
conf
DOI :
10.1109/ICLP.2014.6973112
Filename :
6973112
Link To Document :
بازگشت