DocumentCode
1719583
Title
Simple Circuit Models for Studying Global Earthing Systems
Author
Campoccia, A. ; Zizzo, G.
Author_Institution
Dept. of Electr., Univ. of Palermo, Palermo
fYear
2007
Firstpage
1947
Lastpage
1952
Abstract
The paper proposes three simple circuit models for the simulation of the behaviour of a global earthing system during different fault events. The models allow one the evaluation of the maximum earth potential rise at every possible fault location and for every possible fault event. The three considered fault events are: single-line-to-earth fault inside a MV/LV substation, double-earth-fault in a MV line, single-line-to-earth fault inside a HV/MV station. After having illustrated the hypotheses at the basis of the study, the circuit models for the three fault events are presented and a numerical example shows how to use them in order to check the "global safety" of the interconnected earthing systems.
Keywords
earthing; electrical safety; fault diagnosis; substations; MV-LV substation; double-earth-faults; fault events; global earthing systems; global safety; interconnected earthing systems; maximum earth potential rise; single-line-to-earth faults; Circuit faults; Earth; Electrodes; Fault location; Grounding; Integrated circuit interconnections; Paramagnetic resonance; Safety; Substations; Voltage; Earth Electrodes; Global Earthing Systems; Power System Fault;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech, 2007 IEEE Lausanne
Conference_Location
Lausanne
Print_ISBN
978-1-4244-2189-3
Electronic_ISBN
978-1-4244-2190-9
Type
conf
DOI
10.1109/PCT.2007.4538615
Filename
4538615
Link To Document