• DocumentCode
    1719583
  • Title

    Simple Circuit Models for Studying Global Earthing Systems

  • Author

    Campoccia, A. ; Zizzo, G.

  • Author_Institution
    Dept. of Electr., Univ. of Palermo, Palermo
  • fYear
    2007
  • Firstpage
    1947
  • Lastpage
    1952
  • Abstract
    The paper proposes three simple circuit models for the simulation of the behaviour of a global earthing system during different fault events. The models allow one the evaluation of the maximum earth potential rise at every possible fault location and for every possible fault event. The three considered fault events are: single-line-to-earth fault inside a MV/LV substation, double-earth-fault in a MV line, single-line-to-earth fault inside a HV/MV station. After having illustrated the hypotheses at the basis of the study, the circuit models for the three fault events are presented and a numerical example shows how to use them in order to check the "global safety" of the interconnected earthing systems.
  • Keywords
    earthing; electrical safety; fault diagnosis; substations; MV-LV substation; double-earth-faults; fault events; global earthing systems; global safety; interconnected earthing systems; maximum earth potential rise; single-line-to-earth faults; Circuit faults; Earth; Electrodes; Fault location; Grounding; Integrated circuit interconnections; Paramagnetic resonance; Safety; Substations; Voltage; Earth Electrodes; Global Earthing Systems; Power System Fault;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Tech, 2007 IEEE Lausanne
  • Conference_Location
    Lausanne
  • Print_ISBN
    978-1-4244-2189-3
  • Electronic_ISBN
    978-1-4244-2190-9
  • Type

    conf

  • DOI
    10.1109/PCT.2007.4538615
  • Filename
    4538615