• DocumentCode
    1719896
  • Title

    Application of inverter based shunt device for voltage sag mitigation due to starting of an induction motor load

  • Author

    Huweg, A.F. ; Mieee, S.M.Bashi ; Smieee, N.Mariun

  • Author_Institution
    Universiti Putra Malaysia - Malaysia
  • fYear
    2005
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper shows a study of the static synchronous compensator (STATCOM) behaviors for voltage sag mitigation to an induction motor. The proposed of STATCOM stability model is justified based on the basic operation characteristics of phase control strategies. The simulation of 6 pulses STATCOM based on voltage source inverter (VSI) using Matlab Simulink is presented to show its good performance under balanced voltage sag condition due to the motor starting. Experimental testing has been made by using thyristor firing board control (FS36M). The STATCOM response of compensated reactive power to the system during voltage sag has been shown. Finally simulation results and experimental results have been described and compared once and good performance has been obtained.
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 2005. CIRED 2005. 18th International Conference and Exhibition on
  • Conference_Location
    Turin, Italy
  • Type

    conf

  • Filename
    5427707