DocumentCode :
1720636
Title :
Assessing the impact of increased air conditioner load on power quality in Australia
Author :
Moller, Lianne ; Robinson, Duane ; Perera, Sarath ; Gosbell, Vic ; Bucca, Frank
Author_Institution :
Integral Energy Power Quality and Reliability Centre, University of Wollongong - Australia
fYear :
2005
Firstpage :
1
Lastpage :
5
Abstract :
Measurements of performance of existing technology air conditioner systems with regards to their impact on power quality in LV distribution systems are presented. Three types of split-phase air conditioners are studied including direct on line starting, soft starter and inverter fed units. Results of testing and subsequent calculations illustrate that the direct on line and soft starter units do not meet compliance requirements of the relevant standard, and as penetration of air conditioners increases, voltage fluctuations may become a significant problem in some LV distribution systems in Australia.
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution, 2005. CIRED 2005. 18th International Conference and Exhibition on
Conference_Location :
Turin, Italy