Title :
Calculation of current distribution during direct strikes to lightning protective system
Author :
Ping Wang ; Lin Li
Author_Institution :
State Key Lab. of Alternate Electr. Power Syst. with Renewable Energy Sources, North China Electr. Power Univ., Beijing, China
Abstract :
In order to decide on an efficient lightning protection system, it is very important to determine the lightning current distribution in the building. In this paper, the lightning channel base current adopts the function which is composed of one Heidler´s and one double-exponential function. The lightning current distribution in the LPS is calculated based on the partial element equivalent circuit in the frequency domain. The lightning current distribution in the LPS is also calculated by means of the commercial software CDEGS, and the calculated currents in the LPS are compared with those measured.
Keywords :
building management systems; current distribution; equivalent circuits; frequency-domain analysis; lightning protection; CDEGS commercial software; Heidler; LPS; building direct strike; double-exponential function; efficient lightning protection system; frequency domain; lightning channel base current; lightning current distribution calculation; partial element equivalent circuit; Couplings; Current distribution; Lightning; Lightning protection system; current distribution; lightning channel base current;
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
DOI :
10.1109/ICLP.2014.6973285