    Experiences of unexpected breakdown of current transformers during power frequency withstand test

  • Author

    Pourmohamadiyan, P. ; Sanaye-Pasand, M. ; Jahromi, A.N. ; Rafiei, A.

  • Author_Institution
    Kazeroun Azad Univ., Iran
  • Volume
    1
  • fYear
    2004
  • Firstpage
    494
  • Abstract
    Power frequency withstand test is one of the routine tests which must be performed on the high voltage current transformers in the factory. Special attentions are paid to the measured Partial Discharge (PD) value during increasing voltage and also during application of the specified voltage. The test is stopped if the measured PD value exceeds a specified limit, which is recognized on the basis of experiences. This interruption makes an opportunity to remove the possible CT defects (such as oil degassing) with lower cost, before a sudden occurrence of breakdown in the CT. But in some tests, insulation breakdown occurred in the CT, though no considerable PD value had been detected prior to the breakdown. So, more cost is imposed on the manufacturer to repair and replace the damaged components. The possible major causes of this problem and their corresponding solutions are analyzed in this paper.
  • Keywords
    current transformers; failure analysis; insulation; partial discharges; current transformer breakdown; high voltage current transformers; insulation breakdown; oil degassing; partial discharge value; power frequency withstand test; Costs; Current transformers; Electric breakdown; Frequency; Partial discharge measurement; Partial discharges; Performance evaluation; Petroleum; Production facilities; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2004. ICSD 2004. Proceedings of the 2004 IEEE International Conference on
  • Print_ISBN
    0-7803-8348-6
  • Type

    conf

  • DOI
    10.1109/ICSD.2004.1350398
  • Filename
    1350398