Title :
Estimation of the shielding performance of transmission lines: Comparison of deterministic and probabilistic methods
Author :
Lobato, A.T. ; Schroeder, M.A.O. ; Sales, W.S. ; Nascimento, L.C. ; Assis, S.C.
Author_Institution :
Electr. Eng. Dept., Fed. Univ. of Sao Joao del-Rei, Sao Joao del-Rei, Brazil
Abstract :
The shielding performance of transmission lines is generally evaluated through deterministic methods, e.g. Anderson´ simplified method, which is implemented on IEEE Flash program. However, more accurate results may be observed with a probabilistic approach, e.g. with Monte Carlo Method, at what all random variables associated with lightning interactions with transmission systems are considered by means of probability density functions, e.g. the lightning strike position, leader angle, power frequency voltage, etc. This paper is aimed at contrasting the estimation of the shielding failure flashover rate (SFFOR) resulting from these two procedures, with especial attention on analysing the representativity of the results obtained with IEEE Flash program.
Keywords :
IEEE standards; Monte Carlo methods; deterministic algorithms; flashover; lightning protection; power transmission lines; probability; shielding; Anderson simplified method; IEEE flash program; Monte Carlo method; SFFOR estimation; deterministic method; lightning interaction; probabilistic approach; probability density function; shielding failure flashover rate estimation; transmission lines shielding performance estimation; Ear; Lead; IEEE Flash Program; Monte Carlo method; Shielding failure flashover rate;
Conference_Titel :
Lightning Protection (ICLP), 2014 International Conference o
Conference_Location :
Shanghai
DOI :
10.1109/ICLP.2014.6973435