Title :
AGC Parameter Determination for an Oil Facility Electric System
Author :
Jativa-Ibarra, Jesus ; Morales, Mario I. ; Cabrera, Waldo J. ; Quilumba, Franklin L. ; Wei-Jen Lee
Author_Institution :
Dept. of Electr. Energy, Nat. Polytech. Sch., Quito, Ecuador
Abstract :
It is necessary to accurately estimate parameters to have a better prediction on the response of a generator under different operating conditions. Since automatic generation control (AGC) is closely related to the real power and frequency of the unit, the dynamic parameters that are required by a standard AGC function are determined for the electric system of an oil facility. Speed droop characteristics, governor deadbands, and generation ramp rates are evaluated using field tests on thermal units. Frequency bias for the area control error calculation is also presented. Test procedures for each parameter calculation are described in detail for thermal units of 1, 3, and 3.75 MW installed at Ecuadorian oil well facilities. Test results for these units demonstrate the practicability of the proposed test procedures.
Keywords :
automatic gain control; power generation control; power plants; AGC parameter determination; area control error calculation; automatic generation control; generation ramp rates; governor deadbands; oil facility electric system; speed droop characteristics; thermal units; Automatic generation control; Frequency control; Generators; Steady-state; Time-frequency analysis; Automatic generation control (AGC) parameters; generator ramp rates; governor deadbands (DBs); parameter determination; speed droop characteristics; thermal power units of oil facilities;
Journal_Title :
Industry Applications, IEEE Transactions on
DOI :
10.1109/TIA.2013.2295474