Title
Determination of PD sensitivity of GIS using signal reduction measurements
Author
Meijer, S. ; Gulski, E. ; Smit, J.J. ; Kanters, A.J.L.M.
Author_Institution
High Voltage Lab., Delft Univ. of Technol., Netherlands
Volume
1
fYear
1998
Firstpage
65
Abstract
In this paper aspects of the signal reduction of partial discharge signals in gas insulated substations are discussed. Several examples are used to point out the problems on signal reduction. This discussion is important for the determination of the 5 pC sensitivity of the couplers located anywhere in the substation. It is shown that the signal reduction between two couplers may be influenced by the repetition rate of PD pulses, small differences in the GIS configuration and type of GIS components
Keywords
gas insulated substations; insulation testing; partial discharge measurement; 5 pC sensitivity; GIS; GIS components; PD sensitivity; couplers; gas insulated substations; partial discharge signals; repetition rate; signal reduction measurements; substation; Couplers; EMP radiation effects; Electromagnetic measurements; Geographic Information Systems; Partial discharge measurement; Partial discharges; Pulse generation; Pulse measurements; Signal generators; Substations;