• DocumentCode
    1731103
  • Title

    Evaluating the calibration of UHF couplers for partial discharge detection [gas insulated substations]

  • Author

    Judd, M.D. ; Pearson, J.S.

  • Author_Institution
    Strathclyde Univ., Glasgow, UK
  • Volume
    1
  • fYear
    1998
  • Firstpage
    77
  • Abstract
    The validity of a recently proposed calibration scheme for the UHF couplers that are used to detect partial discharge in gas insulated substations is investigated. The measured UHF pulse power from a coupler is compared with the predicted output power calculated using its calibrated sensitivity. The theoretical basis for the comparison is presented and demonstrated. In an experiment using an external window coupler, the difference between the two values was only 0.3 dB. The results endorse the test procedure and standard conditions adopted for coupler calibration. The use of coupler calibration results to determine the required amplitude of pulses for pulse injection testing of UHF monitoring systems is discussed
  • Keywords
    UHF couplers; UHF measurement; calibration; gas insulated substations; insulation testing; partial discharge measurement; UHF couplers; UHF monitoring systems; UHF pulse power; calibration; calibration scheme; coupler calibration; external window coupler; gas insulated substations; output power; partial discharge detection; pulse injection testing; test procedure; Calibration; Couplers; Gas insulation; Partial discharge measurement; Partial discharges; Power generation; Power measurement; Pulse measurements; Substations; UHF measurements;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1998. Conference Record of the 1998 IEEE International Symposium on
  • Conference_Location
    Arlington, VA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-4927-X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1998.704652
  • Filename
    704652