DocumentCode :
173445
Title :
Bad data detection by dynamic state estimation for the case of low redundancy of measurements
Author :
Glazunova, A.M. ; Kolosok, I.N.
Author_Institution :
Energy Syst. Inst., Irkutsk, Russia
fYear :
2014
fDate :
13-16 May 2014
Firstpage :
407
Lastpage :
412
Abstract :
The paper presents a new approach to the validation of measurement which is based on the use of statistical information. Such information is presented by procedure of the dynamic state estimation. Dynamic state estimation makes it possible to take into account the interrelation among state variables changing in time. The method for validating the measurements is based on the fact that when the variance for the measurements in the state estimation problem is set incorrectly, the estimates will be little better, and in the case of a gross error even worse than the measurements themselves. Moreover, the statistics of the voltage vector estimates will not stabilize.
Keywords :
phasor measurement; power system state estimation; redundancy; statistical analysis; bad data detection; dynamic state estimation; electric power system; statistical information; voltage vector estimation; Measurement uncertainty; Power measurement; Power system dynamics; Reactive power; State estimation; Vectors; Voltage measurement; bad data detection; dynamic state estimation; electric power system; measurements;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Conference (ENERGYCON), 2014 IEEE International
Conference_Location :
Cavtat
Type :
conf
DOI :
10.1109/ENERGYCON.2014.6850459
Filename :
6850459
Link To Document :
بازگشت