Title :
The interpretation of return voltage curves of paper-oil-cables
Author :
Patsch, Rainer ; Jung, Jochen ; Kouzmine, Oleg
Author_Institution :
Inst. of Mater. & Diagnostics in Electr. Eng., Siegen Univ., Germany
Abstract :
The paper reports on return voltage measurements performed on different 10 kV paper-oil insulated belted-type cables used in network systems with isolated neutral and with effective earthing of the neutral. The different cable design, e.g., the increased thickness of insulation between conductor and sheath for isolated systems, has a strong influence on the return voltage curves. Thus, a diagnostic method, which is exclusively based on single parameters such as the maximum or the initial slope of the return voltage curves, may lead to a misinterpretation. A more sophisticated evaluation method, which uses the time dependence of the complete return voltage curve is proposed in this paper
Keywords :
impregnated insulation; insulating oils; insulation testing; paper; power cable insulation; power cable testing; 10 kV; cable design; conductor; diagnostic method; effective earthing; isolated neutral; network systems; paper-oil insulated belted-type cables; paper-oil-cables; return voltage curves; return voltage measurements; sheath; single parameters; time dependence; Cable insulation; Circuits; Conductors; Degradation; Dielectrics and electrical insulation; Grounding; Noise measurement; Performance evaluation; Polarization; Voltage measurement;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 2000 Annual Report Conference on
Conference_Location :
Victoria, BC
Print_ISBN :
0-7803-6413-9
DOI :
10.1109/CEIDP.2000.885222