• DocumentCode
    1738019
  • Title

    Evaluation of the insulation design of polymer housed surge arresters using salt-fog test

  • Author

    Biglar, B. ; Jayaram, S. ; Cherney, E.A.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont., Canada
  • Volume
    1
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    385
  • Abstract
    Insulation design of polymer housed surge arresters for distribution lines are evaluated by using IEC 1109 based salt fog test. The concept of “rest time” in salt fog tests of housings has been introduced with an effort to give fairness to silicone materials. The method provides a comprehensive evaluation of insulation design of polymer housed surge arresters. However, at this time, the inclusion of a rest time in salt-fog tests of silicone rubber housings is not warranted, as hydrophobicity did not recover completely even after a seven-day rest period
  • Keywords
    arresters; composite insulators; environmental testing; ethylene-propylene rubber; insulator testing; leakage currents; polymer insulators; silicone rubber insulators; IEC 1109 based test; average watt loss; distribution lines; hydrophobicity; insulation design; leakage current; polymer housed surge arresters; rest time concept; salt-fog test; silicone rubber housings; Arresters; IEC standards; Insulation testing; Insulator testing; Life testing; Materials testing; Plastic insulation; Polymers; Stress; Surges;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2000 Annual Report Conference on
  • Conference_Location
    Victoria, BC
  • Print_ISBN
    0-7803-6413-9
  • Type

    conf

  • DOI
    10.1109/CEIDP.2000.885306
  • Filename