DocumentCode :
174522
Title :
Experimental tests of High Impedance Faults in MV rural distribution network
Author :
Gonzalez, P. ; Romero, Eduardo ; Minambres, Victor M. ; Guerrero, Miguel A.
Author_Institution :
Electr., Electron. & Autom. Eng. Dept., Univ. of Extremadura, Caceres, Spain
fYear :
2014
fDate :
22-24 May 2014
Firstpage :
1
Lastpage :
10
Abstract :
One of the electrical distribution company´s aim is to maintain the power supply to customers. In rural distribution feeders the proliferation of nest over the electric towers has committed this objective and actually the efforts of electrical companies to maintain clean their lines are huge. The problems occur when parts of nest caused the electrical contact between conductor and steel tower producing High Impedance Faults (HIF) and sometimes tripping protection. In this paper this problem is addresses, experimental tests were carried out in MV feeder to show this type of HIF is detectable from substation and a characterization of signal measured could be used to relay protection reprogramming.
Keywords :
conductors (electric); electric impedance; electricity supply industry; poles and towers; power distribution faults; power distribution protection; relay protection; substation protection; HIF; MV feeder; MV rural distribution network; conductor; electric steel tower; electrical contact; electrical distribution company; high impedance faults; power supply; relay protection reprogramming; rural distribution feeders; substation; tripping protection; Conductors; Contacts; Current measurement; Poles and towers; Substations; Vegetation; Voltage measurement;
fLanguage :