DocumentCode
1750092
Title
Economical 36 kV cable system for the Belgian network
Author
Becker, J. ; Musique, F.
Author_Institution
NEXANS BENELUX S.A., Belgium
Volume
1
fYear
2001
fDate
2001
Abstract
In order to reduce the cost of the 36 kV cable, Electrabel redefined cables in terms of performance rather than construction regulations as in the past. This allowed cable to be designed with lower XLPE insulation and sheath thickness and reduced screen cross-section, which led to a cost reduction of 20% on cables. Tests on the new lean cable with accessories were performed successfully. Several 100 km of the new cables have been installed in the network since the end of 1998. The utilities intend to ask the Belgian Electrotechnical Committee to take the necessary steps to have the new construction of 36 kV cable included in European standards
Keywords
XLPE insulation; cable sheathing; power cable insulation; power cable testing; 36 kV; Belgian Electrotechnical Committee; Belgian network; Electrabel; European standards; XLPE insulation; cable system; cost reduction; screen cross-section reduction; sheath thickness;
fLanguage
English
Publisher
iet
Conference_Titel
Electricity Distribution, 2001. Part 1: Contributions. CIRED. 16th International Conference and Exhibition on (IEE Conf. Publ No. 482)
Conference_Location
Amsterdam
ISSN
0537-9989
Print_ISBN
0-85296-735-7
Type
conf
DOI
10.1049/cp:20010673
Filename
942769