DocumentCode :
1753831
Title :
Traveling-Wave Starting Algorithm Based on Least Square Method
Author :
He, Renwang ; Teng, Jinfen
Author_Institution :
Sch. of Electr. & Electron. Eng., East China Jiaotong Univ., Nanchang, China
fYear :
2011
fDate :
25-28 March 2011
Firstpage :
1
Lastpage :
4
Abstract :
The paper proposes a new method of fault transient signal singularity detection by wavelet transform, analyzes the main drawbacks of present starting algorithms which use only adjacent scale of WTMM of WTMS ratio to determine the Lipschitz coefficients, presents a new method for estimating Lipschitz coefficients based on least square method by fitting the data of various scales. ATP-EMTP simulation results show that the proposed algorithm can more accurately analyze singularity of fault signal.
Keywords :
fault diagnosis; least mean squares methods; power system faults; power system transients; signal detection; wavelet transforms; ATP-EMTP simulation; Lipschitz coefficient estimation; fault transient signal singularity detection; least square method; traveling-wave starting algorithm; wavelet transform; Least squares methods; Power transmission lines; Transient analysis; Wavelet analysis; Wavelet transforms;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2011 Asia-Pacific
Conference_Location :
Wuhan
ISSN :
2157-4839
Print_ISBN :
978-1-4244-6253-7
Type :
conf
DOI :
10.1109/APPEEC.2011.5748912
Filename :
5748912
Link To Document :
بازگشت