• DocumentCode
    1756238
  • Title

    Directional Relaying in the Presence of a Thyristor-Controlled Series Capacitor

  • Author

    Jena, Premalata ; Pradhan, A.K.

  • Author_Institution
    Department of Electrical Engineering, Indian Institute of Technology, Kharagpur, India
  • Volume
    28
  • Issue
    2
  • fYear
    2013
  • fDate
    41365
  • Firstpage
    628
  • Lastpage
    636
  • Abstract
    This paper proposes a fault direction estimation technique for a line with a thyristor-controlled series capacitor (TCSC). Such a compensated line imposes problems to directional relaying schemes due to reactance modulation, current, and voltage inversion issues and TCSC-control action. Three positive-sequence-based classifiers are combined in an integrated approach to estimate the direction of fault for a line with TCSC. The method is tested for different fault situations, such as high resistance fault, close-in fault, as well as voltage and current inversions, and is found to be accurate.
  • Keywords
    Fault currents; Power capacitors; Power systems; Relays; Resistance; Thyristors; Current inversion; digital relay; directional relay; thyristor-controlled series capacitor (TCSC); transmission-line fault; voltage inversion;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2013.2249538
  • Filename