• DocumentCode
    1758841
  • Title

    Paralleled multi-terminal DC transmission line fault locating method based on travelling wave

  • Author

    Jingzhou Cheng ; Minyuan Guan ; Lv Tang ; Hongyang Huang ; Xin Chen ; Jiajia Xie

  • Author_Institution
    Dept. of Electr. Eng., Zhejiang Univ., Hangzhou, China
  • Volume
    8
  • Issue
    12
  • fYear
    2014
  • fDate
    12 2014
  • Firstpage
    2092
  • Lastpage
    2101
  • Abstract
    This study presents a novel protection criterion of fault locating in multi-terminal DC (MTDC) transmission systems. When a fault occurs on the DC transmission line of the MTDC system, the traditional protection cannot locate the fault because there is no smoothing reactor (equipped at the converter output) in the transmission lines. In the circumstance of AC/DC conductor contact (ADCC) fault, the varieties of the transient voltage and current components are given based on the symmetrical fault analysis. According to the Bergeron equation, the travelling wave characteristic is analysed. A new criterion of fault locating using the change rate of the current travelling wave is presented which can reduce the impacts of the related fault on the AC system. Finally, simulation results verify the effectiveness of the proposed protection criterion.
  • Keywords
    AC-DC power convertors; conductors (electric); fault location; power system transients; power transmission faults; power transmission lines; power transmission protection; AC-DC conductor contact fault; ADCC fault; Bergeron equation; MTDC system; converter output; current components; fault locating method; paralleled multiterminal DC transmission line; protection criterion; symmetrical fault analysis; transient voltage; travelling wave;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission & Distribution, IET
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2013.0886
  • Filename
    6985841